Installation Notes – Laying a Split Pipe
Siphon-shaped bending of the split pipes
Caution!
The bends are to be as tight as possible
observing the minimum permissible bend
radius (min. bend radius = 3.5 x outer
diameter of pipe)!
The split pipes can also be led out of the left side
of the indoor component (in the direction of the
pre-bent connection pipe); the thin areas in the
side of the casing must be cut out for this.
¹ Subsequent wrapping of the split pipes with fabric
adhesive tape (or aluminium adhesive tape) protects the
pipe insulation from damage by UV radiation and
mechanical damage (rubbing against masonry, bird bites)
and increases the rigidity of the pipes (if they are both
wrapped together) – we therefore recommend wrapping
the split pipes or laying them in covered conduits!
When laying split pipes, please note that if the difference in height between the indoor
and outdoor components is more than 3 m, the pipes must have a siphon-type bend and
a second siphon bend for a further 3 m difference!